User Manual

29/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.11 Basic setpoints
All RXC applications
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element
Function/Range
BT
User designation NV name NV element
@TCRn.SPCH Comfort heating setpoint
ncoSetpoints . occupied_heat
Occupied heating setpoint
2
Occup Setpts
nciSetpoints occupied_heat
@TCRn.SPRH
Reduced heating
setpoint
ncoSetpoints . standby_heat
Standby heating setpoint
2
Occup Setpts
nciSetpoints
standby_heat
@TCRn.SPEH
Economy heating
setpoint
ncoSetpoints . unoccupied_heat
Unoccupied heating
setpoint
2
Occup Setpts nciSetpoints
unoccupied_heat
@TCRn.SPCC Comfort cooling setpoint
ncoSetpoints . occupied_cool
Occupied cooling setpoint
2
Occup Setpts
nciSetpoints
occupied_cool
@TCRn.SPRC
Reduced cooling
setpoint
ncoSetpoints . standby_cool
Standby cooling setpoint
2
Occup Setpts
nciSetpoints
standby_cool
@TCRn.SPEC
Economy cooling
setpoint
ncoSetpoints . unoccupied_cool
Unoccupied cooling
setpoint
2
Occup Setpts
nciSetpoints
unoccupied_cool
Caution The basic setpoints are stored in a non-volatile memory in the RXC controller with a limited number of write cycles. It is therefore extremely important to avoid frequent
modification of any of these values! Instead of using a time scheduler, for example, to modify the setpoints on the basis of the time of day, the same effect can be
achieved by changes the operating mode (e.g. between Comfort and Pre-comfort. It is also possible to implement temporary setpoint changes via a setpoint shift
(@TCRn.RRSC).
Note From CFE Version V2.1 the basic setpoints can, optionally, be synchronized when the controller is powered on.
Refer to the V2.1 release notes on this subject.
3.2.12 Display effective valve positions
All RXC applications
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name NV element
@TCRn.COVR.OR
@TCRn.OHWA
@TCRn.OXWA
Position of heating or
changeover valve (see diagram)
nviHeatPrimary
Position of primary
heating valve (0…100%)
2
Primary Heat nvoHeatPrimary
@TCRn.OCWA
Position of cooling valve (see
diagram)
nviCoolPrimary
Position of primary cooling
valve (0…100%)
2
Primary Cool
nvoCoolPrimary