User Manual

23/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.3 Definition of room operating mode
All RXC applications
VISONIK BPS NIDES.RX RXC controller
DP.Parameter Function/Range
NV name / element Function/Range
BT
User designation NV name
NV element
@TCRn.SOPST nvoUseSchedule See table of bindings 1
Building Use
Scheduler
nviUseSchedule Current state
@TCRn.MOPST
1)
nvoOccSchedule See table of bindings 1 Occup Scheduler nviOccSchedule Current state
@TCRn.SOMOD
See table of bindings
1)
Manual Operating State: Same function as @TCRn.SOPST when @TCRn.MACT=1
Table of bindings:
@TCRn @TCRn Building Use Occup RXC...
.SOMOD .SOPST Scheduler Scheduler Operating mode
Auto
0 = Local 0 = Comfort Occupied Occupied Comfort Standby Comfort
1 = Reduced Occupied Standby Standby Standby Comfort
2 = Economy Occupied Unoccupied Economy Economy Comfort*
3 = Standby Unoccupied Unoccupied Bldg protection
= Remote ! 0 = Comfort Occupied Occupied Comfort Standby Comfort
! 1 = Reduced Occupied Standby Standby Standby Comfort
2 = Economy Standby Unoccupied Economy
3 = Standby Unoccupied Unoccupied Bldg protection
!
Functions not same as with TEC * Override function (timer acti
o
Not possible
Operation on QAX...
Not possible
RX master (BPS) Network variables RX operator unit
Not possible
RXC controller
Initial state The CFE software @TCRn.SOPST=0 (Comfort) is set after a restart following the loading of a new project.
Note From CFE Version 2.1, the operating mode is only written to the controllers after a restart if the associated option has been set.
For more on this subject, refer to the V2.1 release notes.