User Manual

21/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration functions 12.06.2006
3.2.1 Example of a
read operation
3.2.24 Intranet room operation
All RXC applications
VISONIK BPS NIDES.RX RXC controller
DP. Parameters Function/Range NV name / element Function/Range
BT
User designation NV name NV element
@TCRn.AOPST See "Effective room status" nviEffectOccup
See "Effective room
status"
1
Effect Occup
nvoEffectOccup
@TCRy.ARTP Current room temperature nviSpaceTemp
Current room
temperature
1 Effect Space Temp nvoSpaceTemp
@AOx’24.EMV
Room status: 0 = Occupied
3 = Standby
nvoOccManCmd
Operating mode on
room unit
ne
Occup Override
nviOccManCmd
@AOx’12.EMV
Setpoint adjustment
: -3 ... +3 °C
nvoSetptOffset
Setpoint adjustment
from room unit
ne Setpt Offset nviSetptOffset
@AI x’ 80.EMV
Actual setpoint adjustment
nviSetptOffset
Actual setpoint
adjustment
ne Local Setpt Offset nvoSetptOffset
Shows which RXC
applications can be used
TEC Room parameter
n = Room No. (1..99)
Link point AI / AO, Address x' y ,
x = Controller No. (33..126)
y = Code for function or NV
y = 1..4 : Blind function (AO)
y = 5..8 : Lighting function (AO)
y =11..210 : Single parameter of NV (AI / AO)
Direction of data flow
Standard Binding Template, containing the
relevant network variable:
1 / 2 / ne = Not in any standard binding template
NV name in
NIDES.RX
NV name in
RXC controller
Definition of RS
master function
Former designation for network variablein the
Binding Template Editor of the RXT10 tool.
Now only found in the documentation.