User Manual

17/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration overview 12.06.2006
2.8 Preliminary hardware list
The table below shows a preliminary hardware list. It provides the following information
for the various applications, and can therefore be used for a preliminary estimate when
preparing a quotation.
Possible number of RXC controllers per NIDES
Number of VISONIK points in the BPS
Application Number of DESIGO RX
controllers
per NIDES
VISONIK VISONIK
Template 1 Template 2
Approx. number of
VISONIK points
in RX master
Radiator-type systems 80 47 … 50 140 … 240
Radiator / chilled ceilings 80 47 … 50 135 … 240
Fan-coil units 80 42 … 47 120 … 240
Integrated application
(HVAC, blinds, lighting)
42 … 60 30 … 39 220 … 420
VAV 80 42 ... 50 120 ... 240
Note the following in relation to the information in the table:
Where the number of RXC controllers is given as a range, this is because individual
applications in the category concerned have a different number of network variables
(as for example in VISONIK Template 2 for applications RAD01 and RAD03 in the
“Radiators” category).
The estimate of the number of controllers per NIDES is based on a maximum of 900
RS data points in the NIDES. However, it is advisable to plan a reserve capacity of
10% . (in other words, to use no more than 800 data points, if possible) to
accommodate future changes and enhancements etc.
The term “VISONIK points” refers to TEC points and link points. These must not
exceed 500 in number.
For a guide to detailed calculation refer to Section 4, "Engineering".
This will help you determine more precise quantities, taking the following into account:
Different applications (mixed)
Additional RS master functions to be integrated from the extended selection.
Overview
Notes on the overview
Detailed calculation