User Manual
14/90
Building Technologies Integration von DESIGO™ RXC in VISONIK CM2Z8338en_01
Building Automation Integration overview 12.06.2006
2.5 RX master functions with VISONIK templates 1 / 2
VISONIK Templates 1 and 2 are stored in the RXT10 as default templates for
integration into the NIDES.RX. The difference between the two templates is as follows:
– VISONIK Template 1 contains the main functions for HVAC, blinds and lighting
– VISONIK Template 2 incorporates additional HVAC functions
These functions are described in detail in the two tables below.
The following shows the RX master functions for HVAC applications, available when
using VISONIK Templates 1 and 2. The additional functions offered by Template 2 are
shown on a shaded background.
Template
1
Template
2
RX master function
9 9
Definition of the HVAC operating modes:
Comfort, Pre-comfort, Economy, Standby
9 9
Display of current operating mode and associated current
setpoints
9
Read/Write cooling and heating setpoints
9 9
Summer/winter compensation and room setpoint shift
9 9
Display current room temperature
9
Display of valve positions
9
Display current volumetric air flow
9
Display current fan speed
9 9
Display of controller status:
Normal / Fault
9 9
Room temperature monitoring
(TEC function, needs to be configured)
9 9
Optimum Start Program
(TEC function, needs to be configured)
9 9
Summer/winter changeover
9 9
Define controller operating mode: Heating, Cooling, Night
purge etc.
The next table shows the basic functions for blinds and lighting. Both Template 1 and
Template 2 incorporate these functions.
Template
1
Template
2
RX master functions
9 9
Display of effective blind status of blinds 1 to 4
9 9
“Local” / “Remote” command for blinds 1 to 4
9 9
Display of effective lighting status of blinds 1 to 4
9 9
“Local”/“Remote” command for lighting zones 1 to 4
Introduction
HVAC functions
Blinds and lighting