Siemens RXC10 – Room controller CA2N3830en_06
Building Technologies 2015-12-23
Standard RJ45 tool socket for LONWORKS® devices.
1
3206Z01
2 3 4 5 6 7 8
1 L
ONWORKS®, Data A (CLA)
2 L
ONWORKS®, Data B (CLB)
3 Not used
4 Not used
5 Not used
6 Not used
7 Not used
8 Not used
Connection diagrams
GND
D1
GND
G
G0
YC1
Y1
CLA
CLB
G
Y2
AC 24 V
0 ... 10 V
D2
LonWorks® Bus
3830A02
CLA L
ONWORKS® data cable +
CLB L
ONWORKS®data cable –
D1, D2 Volt-free contacts (window contact, occupancy detector etc.)
G AC 24 V phase
G0, GND System neutral
Y1, Y2 AC 24 V triac output
YC1 0 … 10 V analogue output
Twisted pair
For information on compatible actuators for the RXC10 controller, refer to the relevant
application description. See Applications library (V1: CA2A3810, V2:CA110300).
Tool socket
Connection of field
devices, L
ONWORKS®
bus and supply voltage