User Manual
7/12
Siemens RXC10 – Room controller CA2N3830en_06
Building Technologies 2015-12-23
Ports
L
ONWORKS® bus
Interface type
L
ONMARK®-compatible,
electrically isolated
Transceiver
On RXC10.1:
FTT-10A
On RXC10.5: FT 5000
Baud rate
78 kBit/s
Bus topology, bus termination
See installation guide, CA110334
Cable connections
Connection terminals
Stranded or solid conductors
0.25 … 2.5 mm
2
or 2 x 1.5 mm
2
solid
Cable lengths
See installation guide, CA110334
Signal inputs D1, D2
Max. 100 m with diameters ≥ 0.6 mm
Triac outputs Y1, Y2
Max. 100m where A ≥ 1.5 mm
2
LONWORKS® bus
See installation guide, CA110334
Cable type
See installation guide, CA110334
Tool connecting cable
Max. 3 m
Protection data
Housing protection standard
IP 30 to EN 60529
Protection class
III to EN 60730-1
Ambient conditions
Operation
Class 3K3 to IEC 60721-3-3
Temperature
5 ... 40 °C
Humidity
< 85 %rh
Transport
Class 2K3 to IEC 60721-3-2
Temperature
– 25 ... 65 °C
Humidity
< 95 %rh
Standards, directiv
es and
approvals
Product standard
EN 60730-1
Automatic electrical controls for
household and similar use
Electromagnetic compatibility (Applications)
For use in residential, commerce, light
-
industrial and industrial environments
EU conformity (CE)
CA2T3830xx *)
UL certification (US)
UL 916, http://ul.com/database
RCM-conformity (EMC)
CA2T3834en_C1 *)
EAC conformity
Eurasia conformity
Environmental
compatibility
Product environmental declaration (contain
s
data on RoHS compliance, materials compo
-
sition, packaging, environmental benefit,
disposal)
CA2E3830 *)
Dimensions
See dimension diagrams
Color
Front plate
NCS S 0502
-G
≈ RAL 9003 signal white
Housing base and mounting plate
RAL 7035 light grey
Weight
Weight excluding packaging
0.16 kg
*) The documents can be downloaded from