User Manual

6/12
Siemens RXC10 Room controller CA2N3830en_06
Building Technologies 2015-12-23
The labeling fields “Appl.” and “Loc.” are used to indicate the application actually loaded
and the location of the controller, either in writing or by use of printed adhesive labels
(see “Label” under “Mechanical design”).
With all applications (including basic application 00010), the inputs can be interrogated
and the outputs overridden using the RXT10 commissioning and service tool.
Technical data
Power supply
Operating voltage
AC 24 V ± 20%
(SELV / PELV) or
AC 24 V class 2 (US)
Frequency
50/60 Hz
Power consumption
Max. 2 VA + external load
Caution!
Internal fuse
None
External supply line protection (EU)
Fuse slow max. 10 A
or
Circuit breaker max. 13 A
Characteristic B, C, D according to
EN
60898 or
Power source with current limitation of
max. 10 A
Operating data
Control algorithm
PI or PID
Temperature sensor
NTC resistance sensor
Measuring range
5 … 40°C
Response time
8 min
Measuring accuracy (25 °C)
± 0.25 °C
Measuring accuracy (0 … 30 °C)
± 0.5 °C
Setpoint correction
Correction range
max. ± 12 K (default ± 3 K)
Accuracy over full correction range
10%
Inputs
Signal inputs D1, D2
Quantity
2
(for volt-free contacts)
Contact voltage
Approx. DC 30 V (pulsed)
Contact current
Approx. DC 10 mA (pulsed)
Contact transfer resistance
Max. 100
Contact insulation resistance
Min. 50 k
Not suitable for pulse control
Outputs
Triac ouptuts Y1, Y2
Quantity
2
Output voltage
AC 24 V ON/OFF, PDM or 3
-position
(depending on application parameters)
Load current per triac
Max. 0.5 A
T
otal nominal load
(with load at both
outputs simultaneously)
Max. 9.5 VA
(e.g. 2 thermic valves, type STE72 per
heating and cooling sequence
Internal fuse
2 A (both outputs together)
Control output YC1
Quantity
1
Nominal voltage range
DC 0 … 10V
Overrange
0.5 V
Resolution
8 bits (50 mV)
Output current
Max. 1 mA
Response time
100 ms
Labeling
Function test