User Manual

17
Integration into the building automation
and control system
Management
level
Automation
level
Room level
10333Z02_01
BACnet / LonTalk
DESIGO INSIGHT
RXC...
QAX5...
PPS2
QAX...
ON ARK
LM / LonTalk
RXC...
DESIGO INSIGHT
PXM20-E
PXM20
BACnet / LonTalk
PXX-Lxx
PXC....D modular
PXX-Lxx
PXC200-E.D
BACnet / Ethernet / IP
PXC22.D
PXC....D modular
ON ARK
LM -compatible third-party devices
Stand-alone operation at field level
The Desigo RXC room automation system can be operated as a stand-alone system.
All the required functions are made possible by means of LON communications be-
tween the devices.
Integration into the automation level
Through integration into the Desigo PX automation level, a number of further functions
become available (refer to the PX system description, document CM110756).
The room level is integrated into the automation level by means of the system controller
PXC....D + PXX-Lxx. This controller converts the L
ONMARK objects into BACnet objects,
and provides comprehensive grouping functions. Up to 60 room controllers can be
connected to each PXX-L11 system controller, and up to 120 to each PXX-L12 system
controller.
Features of the system controllers PXC....D + PXX-Lxx:
Concentration of data of the room controllers, and easy manipulation of this data
Simple definition of groups
Implementation of system functions, e.g. time schedules, trends, alarms etc.
Coordination with the primary plant
Efficient engineering and rational commissioning
Features of the PXM20 / PXM20-E operator unit
Operation and monitoring of the entire automation level including inputs, outputs and
the room-controller operating states.
Display and modification of time schedules
Graphics-based display of trend data