Engineering
Topology
Tree, line, or star
NO closed loops
Cable length
Max. 1000 m (sum of all cables of a line
(for details refer to document CM110381)
Cable type
E.g. YCYM 2 x 2 x 0.8 mm
Number
of RXB Controllers per
Network
Max. 45
Bus supply
Up to 45 RXB-controllers:
5WG1 125-1AB12
Bus terminator
Not required
The RXB39.1 room controller operates with a mains supply voltage of AC 230 V.
The sizing and fuse protection of the power supply cables depend on the total
load and on local regulations.
If serial wiring is applied on the terminal block L / N, the connection will be inter-
rupted if the block is removed from the controller (the jumpers 19-19 and 21-21
are on the PCB, not in the block, see terminal diagrams on page 10)
Different phases may be connected to the terminals 21 (L), 23 (Q13) and
26 (Q33).
All AC 230 V conductors must be secured with cable ties.
The volt-free releasing relay output for the fan allows the switching of a load up
to AC 250 V, 5(4) A.
The volt-free releasing relay output for the heating coil switches a resistive load
up to 1.8 kW, max. 10 A.
The circuits must be externally fused ( 10 A) as there are no internal fuses.
The cables connected to the room controller must be secured with cable ties.
The DC 0 … 10 V control outputs YC1, YC2 deliver max 1.5 mA.
The AC 24 V supply output G (next to YC2) delivers max. 6 VA.
The DC 0 … 10 V control output YC3 delivers max 1.5 mA.
The controlled devices (valve and damper actuators) receive their power directly
from the room controller. This means that a separate AC 24 V supply is only
necessary for the field devices require more than a total of 6 VA.
KNX bus
AC 230 V
supply cables
Volt-free
relay outputs
AC 230 V
DC 0...10 V outputs
Valve actuators
Fan control
AC 24 V supply for
field devices (G)