Operating Instructions

Table Of Contents
92/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Control sequences 21 Sep 2010
8.3 Chilled ceiling and radiator 4-pipe (CLC02)
The applications for chilled ceiling and radiator (4-pipe) each have a continuous heating
and cooling sequence. The room controllers operate with a PI algorithm optimized for
thermal or motorized valve actuators. (For simplicity, the diagram below only shows the
P-control action.)
The control sequences come into operation at the effective setpoints for heating and
cooling (see page 67).
100
0
TR [°C]
Y [%]
SpH SpC
YC
YH
H
C
80257
Y Output signal
TR Room temperature
SpH Effective heating setpoint
SpC Effective cooling setpoint
H Heating sequence
C Cooling sequence
YH Heating valve
YC Cooling valve
8.3.1 Configuration and parameterization
Configure the chilled ceiling as described in section 8.1.
Configure the radiator as described in section 8.1.5.
For CLC02, no electromechanic actuators are permitted due to load. (FNC: 10, 12,
18)
Also, thermal valves cannot run parallel operation of Y1 / Y2 and Y3 / Y4.
Notes