Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Control sequences 21 Sep 2010
Select Sequences, Other setpoints:
Select
Sequences, Other setpoints:
HandyTool See the parameters in the last column of the following table.
Parameter for downdraft
compensation
Basic
setting
Range
Resolution
Parameter
HandyTool
Outside temp 0% valve pos 0 °C –30 … 10 °C 0.5 K *078
Outside temp max valve pos –10 °C –30 … 10 °C 0.5 K *079
Maximum valve pos 100% 0 ... 100% 1% *080
The following conditions must be fulfilled:
The room controller must be in
Comfort room operating mode.
ETS3 Professional
ACS Service
Enable the function