Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Introduction 21 Sep 2010
1.7.2 LTE mode
LTE mode was specifically designed to simplify engineering. Unlike with S-mode, there
is no need to create the individual connections (group addresses) in the tool. The
devices establish the connections themselves.
To make this possible, the following was defined:
Every device or sub-device is located within a zone.
Every data point (input or output) is assigned to a zone.
Every data point (input or output) has a precisely defined name.
Whenever an output and an input with the same name are located in the same zone, a
connection is established automatically as shown in the following diagram.
Controller
Valve
Sensor
Time switch zone 1. 1. 1
Outside temperature zone 3
Geogr. zone 2.5.1Geogr. zone 2.5.1
Heat distr zone 1
Cooling coil
Outside temperature
10385Z01en
Outside temperature
Cooling coil
Outside temperature zone 3
The following types of zone are defined:
Geographical zones. (Syntax: Apartment . Room . Subzone).
The time-switch zone is a geographical zone used for special purposes.
Outside temperature zones.
Heat distribution zones.
Refrigeration distribution zones.
For further details, refer to the Konnex specification.
Definitions
Types of zone