Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Temperature measurement 21 Sep 2010
7.2 Outside air temperature via Konnex
bus (CLC02, RAD01)
The outside air temperature must be provided as bus information to all applications with
radiators. It can be read via the following S-mode communication object:
Outside temperature (input communication object)
Flags
R W C T U
Type Receive timeout Value
0 1 1 1 1 9.001
DPT_Value_Temp
Yes Floating point (°C)
Subject to the appropriate configuration and integration, the outside air temperature is
read by the controller immediately after a reset.
In LTE mode, the outside temperature is sent in a zone intended specifically for that
purpose.
Outside temperature input (input)
Possible partner function blocks) Known partner devices
TempOutside
Outside temperature
zone
320 OTS
Room Temperature Sensor
Siemens:
Synco RMH760
RMU710 / 20 / 30
RMB795 / RMS705
KNX
R
CO