Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Temperature measurement 21 Sep 2010
Select tab General functions, Temperature sensor B1 (see page 100).
Select
General functions, Temperature sensor r B1 (see page 100).
HandyTool See the parameters in the last column of the following table.
Short name Basic setting Parameter
Temperature sensor B1 No sensor *092
Room 1
Only meas val acquisition 3
No sensor 255
Only meas val acquisition: Use of the signal: see "analog input B1", page 112.
7.1.3 Averaging analog input & PPS2 interface
In large spaces it can be useful to measure the room temperature in two locations and
to determine an average value. If both a QAX3… room unit and a QAA24 LG-Ni1000
sensor are connected to a controller, the measured room temperature is automatically
based on the average value from both sensors. Automatic detection prevents
miscalculation.
A QAX34 / QAX84 will display this average value.
PPS2 (CP+, CP-)
B1
QAX3...
RXB2...
QAA24
10385Z14
The average value is calculated from the two sensor readings.
To determine the average value, the sensor must be configured as a room
temperature sensor
There is no averaging in KNX sensors.
7.1.4 Sensor correction
The value of the local sensors (PPS2 and B1) can be corrected in the tools
(see page 115).
ETS3 Professional
ACS Service