1.6 Bus supply for RXB Konnex controllers
RXB controllers work without bus supply if the following conditions are adhered to:
Parameterize only using the Handy Tool (not with ETS3 or ACS).
No integration in a building automation and control system (e.g. DESIGO, Synco).
No changeover operation (sensor signal via bus).
No outdoor temperature via bus.
No master/slave combinations.
Else, the Konnex bus, used by RXB room controllers for communications, requires a
bus supply.
Each controller consumes 5 mA. Thus, select the supply according to the number of
controllers. We recommend the following products:
Manufacturer Type Designation
Siemens Building Technologies ACX95.320/ALG Power supply 320 mA
Siemens Automation and Drives 5WG1 125-1AB01 Power supply 160 mA
5WG1 125-1AB11 Power supply 320 mA
5WG1 125-1AB21 Power supply 640 mA
1.7 RXB Konnex controller communications
The RXB Konnex controllers support communications as defined in the Konnex
specification.
This specification defines the following modes among others:
S-Mode = System mode.
LTE mode= Logical Tag Extended Mode
This is a new mode which supports simpler engineering and is used
with Synco.
1.7.1 S-Mode
This mode corresponds to EIB communications. Connections are established via ETS3
Professional and group addresses.
This ensures a link to the existing EIB environment.