Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
68/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Setpoint calculation 21 Sep 2010
6.1.1 Bus output for current setpoints
The present setpoints can be integrated in a building automation and control system
individually or as triplets via the following S-mode communication objects:
Present Eco cooling setp (output communication object)
Present Precomf cool setp (output communication object)
Present Comf cooling setp (output communication object)
Present Comf heating setp (output communication object)
Present Precomf heat setp (output communication object)
Present Eco heat setp (output communication object)
Flags
R W C T U
Type Send
heartbeat
Values
1 0 1 1 0 9.001
DPT_Value_Temp
Yes
Floating Point (°C)
Present setpoints heating (output communication object)
Present setpoints cooling (output communication object)
Flags
R W C T U
Type Send
heartbeat
Values
1 0 1 1 0 222.100
DPT_TempRoomSetpSetF16[3]
Yes 3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
6.1.2 Bus output effective setoints
Upon integration in a building automation and control system, the
effective setpoints
are mapped by the controller to the following communication objects based on the
Effective room operating mode:
Effective setpoint (output communication object)
Effective setpoint heating (output communication object)
Effective setpoint cooling (output communication object)
Flags
R W C T U
Type Send heartbeat Values
1 0 1 1 0 9.001
DPT_Value_Temp
Yes Floating point (°C)
If the room temperature is in the deadband, the
Effective setpoint is transmitted either
as heating or cooling setpoint, depending on whether the controller last was cooling or
heating.
6.1.3 Bus outputs LTE mode
In LTE mode, the current and effective setpoints are not transmitted to the building
automation and control system.
KNX
R
CO
Note