Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
65/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room operating modes 21 Sep 2010
Existing Effective
room op. mode
Room unit
display
Manual operation of
/Auto button
New Effective room
operating mode
Comfort Auto
Precomfort
if
Effective occupancy
= Occupied.
Economy
if
Effective occupancy
= Unoccupied.
Precomfort
Auto Comfort.
Economy
Auto Comfort for Temporary
Comfort period
1)
.
Protection
Auto Protection, unchanged.
Key:
Auto means: "changes to Auto ".
1)
Comfort mode is active for the predefined Temporary Comfort period (see page
103). The room controller then returns to
Economy.
5.6.4 Example for stand-alone
The example below shows how local influences interact to affect the room operating
mode.
Window contacts are installed in all rooms.
If the window is opened (1), the room operating mode changes to Protection and the
room unit is switched again to
.
Room 1 has a room unit.
As no presence detector is connected, the basic room operating mode is
Precomfort
and the timer (Temporary Comfort mode time, see page 103) is thus not available.
The room unit allo
ws for switching between
Precomfort and Comfort (2).
Room 2 has a room unit and a presence detector.
If unoccupied, the basic room operating mode is
Economy; if occupied, the room
operating mode changes to
Comfort (3) and the room unit is set to Auto.
The room unit allows for switching between
Comfort and Precomfort (2).
Room 3: To force the basic room operating mode Economy, a presence detector in
state
unoccupied is simulated at an open digital input (occupied = contact closed,
see page 102).
The timer is available from
Economy.
The room has a room unit on which the timer is activated (Temporary Comfort
mode
period: see page 103). This is where the room operating mode is set to
Comfort (2); when the window is opened (3), after timer expiration (4), or after
pressing again the
/Auto button (5), the room operating mode returns to Economy.