Operating Instructions

Table Of Contents
57/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room operating modes 21 Sep 2010
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible partner function blocks) Known partner devices
EnableComfort
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programs to HVAC-Mode Conversion
Siemens:
Synco RMB795
Possible states are:
State Description
Enabled Priority 3 influences (room operating mode input,
presence detector, room unit) are enabled.
Disabled Priority 3 influences are disabled.
The effective room operating mode is
Economy.
Comfort and Precomfort are enabled locally in the controller with the following
parameter in the
Room unit menu on page 114.
Parameter: Local Comfort mode Description HandyTool
Change from Economy to Precomfort or Comfort mode. *105
Enabled (basic setting)
Precomfort or Comfort can be disabled via the Enable
Comfort
input.
1
Disabled (ignore Enable Comfort input). Precomfort or
Comfort CANNOT be disabled via the Enable Comfort
input.
0
5.5.3 Central control of room operating mode via
room operating mode input
PPS2
Central
(Synco controller)
Local
1.
2.
3.
DI
DI
3.
Controller
3.
Prio
1.
Central (ACS)
0.
The following LTE mode communication object is used
to control the
room operating mode from a building
automation and control system:
Room operating mode (input)
Possible partner function blocks) Known partner devices
HVACMode
Timeswitch zone
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programs to HVAC-Mode Conversion
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
KNX
R
CO
KNX
R
CO