Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room operating modes 21 Sep 2010
The table below shows the effect of the Temporary Comfort mode on the Effective
room operating mode
of the room controller.
Existing Effective
room op. mode
Temporary Comfort
mode
New Effective room
operating mode
Comfort
0 = Not used
No effect.
Precomfort
1 = Trigger
Comfort.
Economy
1 = Trigger
Comfort for Temporary
Comfort period
1)
.
Protection.
1 = Trigger
Protection, unchanged.
Key:
1 means: "changes to 1 ".
1)
Comfort mode is active for the predefined Temporary Comfort period (see page
103). The room controller then returns to
Economy.
5.4.7 Effective room operating mode
PPS2
S
Central Local
1.
3.
S
DI
S
S
DI
3.
Controller
1.
3.
Prio
3.
S
S
The resultant
Effective room operating mode is
available to the building automation and control
system in the following communication objects.
These are for display only and cannot be influenced.
Effective room operating mode (output communication object)
Flags
R W C T U
Type Send heartbeat States
1 0 1 1 0 20.102
DPT_HVACMode
Yes 1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
The resultant
Effective room operating mode is also available as 4 digital
communication objects:
Effective room operating mode Comfort (output communication object)
Effective room operating mode Precomfort (output communication object)
Effective room operating mode Economy (output communication object)
Effective room operating mode Protection (output communication object)
Flags
R W C T U
Type Send heartbeat States
1 0 1 1 0 1.001
DPT_Switch
Yes 0 = Off
1 = On