Operating Instructions

Table Of Contents
41/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room operating modes 21 Sep 2010
The communication object Temporary Comfort mode has two possible states:
State Description
1 = Trigger
Effective room operating mode is Comfort.
0 = Not used
Has no influence on the
Effective room operating mode.
The change in the Effective room operating mode with Temporary Comfort mode
only during the building-in-use period (Use schedule).
The change in the Effective room operating mode is event-driven at the moment
when the communication object is received.
The Effective occupancy or the room unit (both priority 3) can cause the Effective
room operating mode
to change again last command wins.
The table below shows the effect of the
Temporary Comfort mode on the Effective
room operating mode
of the room controller.
Existing Effective
room op. mode
Temporary Comfort
mode
New Effective room operating
mode
Comfort
0 = Not used
No effect.
Precomfort
1 = Trigger
Comfort.
Economy
1 = Trigger
Comfort for Temporary Comfort
period
1)
.
Protection
1 = Trigger
Protection, unchanged.
Key:
1 means: "changes to 1 ".
1)
Comfort mode is active for the predefined Temporary Comfort period (see page
103). The room controller then returns to
Economy.
5.3.7 Effective room operating mode
KNX
R
CO
S
Central Local
1.
2.
3.
S
DI
S
S
S
DI
S
3.
Controller
Prio
PPS2
3.
S
The resultant
Effective room operating mode is
available to the building automation and control
system in the following communication objects.
These are for display only and cannot be influenced.
Effective room operating mode (output communication object)
Flags
R W C T U
Type Send heartbeat States
1 0 1 1 0 20.102
DPT_HVACMode
Yes 1 = Comfort
2 = Precomfort
3 = Economy
4 = Protection
Effective room operating
mode