Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
31/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room operating modes 21 Sep 2010
5 Room operating modes
5.1 Description
The operating modes in DESIGO RXB are Comfort, Precomfort, Economy and
Protection.
In addition, the controller has a frost Protection limit, at which an alarm can
be triggered. Each room operating mode has separately adjustable heating and cooling
sequence setpoints.
Heating Cooling
Y [%]
100
0
TR
10385D01
Comfort
Precomfort
Economy
Protection
Frost risk
Y Output signal (valve or damper actuator).
TR Room temperature.
Comfort is the room operating mode in an occupied room. The room temperature is
within the Comfort range. The room controller operates in the heating or cooling
sequence with the resultant
Comfort setpoints.
In
Precomfort room operating mode (in an unoccupied room), control uses setpoints
that are slightly under the
Comfort setpoint for heating and slightly above for cooling.
Comment: Since
Standby is used in standardization specifically for boiler standby, we
now use the term
Precomfort for the room operating mode.
(Exception: The switching state in the schedule room occupancy is still referred to as
Standby).
If a room is unoccupied for an extended period of time (e.g. night setpoint via
schedules, see pages 35, 47, 57), energy supply to the room can be reduced
significantly. I
n the
Economy room operating mode, control uses setpoints that are
slightly under the Precomfort setpoint for heating and slightly above for cooling.
If the building is unoccupied over an extended period of time (e.g. vacation), the
temperature setpoints can be reduced or raised so that the building and all equipment
are protected against heat or cold at any time.
If the room temperature drops below the
risk of frost limit value, an alarm is triggered
that can be further proceeds in the building automation and control system.
The room controller continues to operate at the relevant setpoint (e.g.
Protection,
Economy, etc.).
The alarm value in the controller is set to 5 °C.
Comfort
Precomfort
Economy
Protection
Risk of frost limit