Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Select communications mode 21 Sep 2010
Let us know look at the floor plan for company Sport AG.
The company required separation of the rooms into two room groups or two
geographical zones (apartm) as follows:
Conference room (room group 1).
All other offices (room group 2).
The RXB room controllers were entered in the floor plan, and the addresses assigned
accordingly:
D: 110
G: 2.1.1
D: 111
G: 2.2.1
D: 112
G: 2.3.1
D: 113
G: 2.4.1
D: 114
G: 1.1.1
RMB795
309
308
307
xx xxx
QQ
x xx
12
Raumgruppe 2
xx xxx
QQ
x xx
12
Room group 1
SA
EA
Relay
Setpoint prio
Enable
Conference
Sport Ltd
10385Z04en
Room group 2
Relay
Setpoint prio
SA
EA
Enable
Office
Office
Conference
room
Office
D = Device address, G = Geographical zone (Apartment . Room . Subzone).
On the KNX bus, several rooms are summarized in a room group via geographical
zone addressing. This address comprises three parts:
Geographical zone: Apartment . Room . Subzone (e.g. 2 . 1 . 1)
A geographical zone must be assigned:
To each RXB room controller.
To each room group of the RMB795 control station.
Here, all devices to be part of the same room group must have the same
apartment number.
The RMB795 control unit only allows for setting the room group, i.e. the geographical
zone (apartment).
Two room groups for
Sport AG
Key
Room group definition
Important!
Settings on the control
unit