Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Select communications mode 21 Sep 2010
The zones are defined under Communication.
Individual zones can also be disabled via command if they are not being used. This has
the advantage of reducing the load on the bus.
HandyTool See the parameter in the last column of the following table.
Short name Basic setting Parameter
Geogr zone (ap) –1 (out of service) *008
Geogr zone (room) 1 *009
Geogr zone (subz) 1 *010
T'swi zone (apartm) 1 *011
TS zone (room) 1 *012
TS zone (subzone) 1 *013
Heat distr zone –1 (out of service) *016
Refrig distr zone –1 (out of service) *017
Outside temp zone 1 *018
Value 0 means broadcast and is thus not allowed.
If the geogr zone or a TS zone has value = -1 for one of the three values, the entire
zone is out of service.
ACS Professional
Reduce bus load
Notes