Operating Instructions

Table Of Contents
14/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Definitions / Tools 21 Sep 2010
2.5.1 Operating HandyTool functions
Function of the buttons
10385Z70
+ = Count / move up.
= Count / move down.
> = Escape (leave unconfirmed).
< = Enter (confirm).
Display
Parameter position. e.g. P006
Value to be adjusted. e.g. 22.5 (a temperature).
or 250 (e.g. a particular type of actuator).
The controller is restarted if certain configuration parameters are changed (e.g. *063
Actuator type).
2.5.2 Minor parameterization using room unit QAX34.3
Start parameterization mode:
Press buttons < , > and – simultaneously for about 2 s until the display turns dark.
Release the buttons.
Press button – twice briefly.
The display now shows
0 (mode 0).
Use + and / or – to choose between the following modes:
0 = Normal mode (normal room unit functions).
2 = Display mode:
The parameters are displayed with prefix "d" (e.g. d015).
Press +/– to find the number and confirm with < (Enter).
This displays the corresponding value.
Press < (Enter) or > (Escape) to return to the list.
3 = Parameterization mode
Allows you to set selected parameters (see below).
They are displayed with prefix "P", e.g. P002.
Press +/– to find the number and confirm with < (Enter).
This displays the corresponding value.
Press +/– to change the value and confirm with < (Enter).
Press > (Escape) to return to the selection without changing anything.
Press Escape again to return to the mode selection.
Press Escape again to return to Normal mode (room unit).
The numbers of the parameters are listed in sections 12.7 and 12.8, and in the
descriptions of
the functions.
A table of parameters with enumerations fort he HandyTool is shown in Section 12.9.
Ne
w start following
important parameter
changes