Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
122/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies KNX information 21 Sep 2010
12.7 HandyTool parameters by number
Visible CC-02
Parameter no.
Description
Name
d = Display (display only)
(mode 2)
P = Parameter (mode 3)
("Minor parameterization")
S = Service(mode 6)
("Major parameterization")
RAD01
CLC01
CLC02
001 16 Physical address (area address) d P S X X X
002 16 Physical address (line address) d P S X X X
003 16 Physical address (device address) d P S X X X
005 30 Plant type d S X X X
006 21 Communication mode d S X X X
008 23 Geographical zone (apartment) d P S X X X
009 23 Geographical zone (room) d P S X X X
010 23 Geographical zone (subzone) d P S X X X
011 23 Time switch zone (apartment) d P S X X X
012 23 Time switch zone (room) d P S X X X
013 23 Time switch zone (subzone) d P S X X X
016 23 Heat distr zone heating surface d P S X
X
*)
X
017 23 Refrig distr zone cooling surface d P S
X
*)
XX
018 23 Outside temperature zone d P S X
X
*)
X
021 98 Master/slave d P S X X X
022 98 Master/slave zone (apartment) d S X X X
023 98 Master/slave zone (room) d P S X X X
024 98 Master/slave zone (subzone) d S X X X
030 70 Protection cooling setpoint d S X X
031 70 Economy cooling setpoint d P S X X
032 70 Precomfort cooling setpoint d P S X X
033 70 Comfort cooling setpoint d P S X X
034 70 Comfort heating setpoint d P S X X
035 70 Precomfort heating setpoint d P S X X
036 70 Economy heating setpoint d P S X X
037 70 Protection heating setpoint d S X X
051 87 Actuator type cool surf valve d S X X
052 88 Running time cool surface valve d S X X
054 88 Offset cooling surface valve d S X X
063 81 Actuator type heat surf valve d S X X
064 82 Running time heat surface valve d S X X
066 82 Offset heating surface valve d S X X
078 86 Outside temp 0% valve pos d S X X
079 86 Outside temp max valve pos d S X X
080 86 Maximum valve pos d S X X