Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
119/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies KNX information 21 Sep 2010
12.5 S-mode communication objects for RAD/CLC
12.5.1 S-mode input communication objects
Flags: R Read
T Transmit
W Write
U Update
C Communication
1)
C.S. = Company specific
For internal use only
Name Flags: Data point type (KONNEX) Receive See
R W C T U timeout Page
Application mode 0 1 1 0 0 20.105 DPT_HVACContrMode Yes 105
Comfort cooling setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Comfort heating setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Cooling surface valve override 0 1 1 0 0 8.010 DPT_Percent_V16 No 90, 93,
103
Economy cooling setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Economy heating setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Enable alarm info 0 1 1 0 0 1.003 DPT_Enable Yes 109
Heating surface valve override 0 1 1 0 0 8.010 DPT_Percent_V16 No 93, 103
Master/slave HVAC controller
input
0 1 1 0 0 C.S.
1)
13 Byte Yes 95
Master/slave room unit input 0 1 1 0 0 C.S.
1)
4 Byte Yes 95
Outside temperature 0 1 1 1 1 9.001 DPT_Value_Temp Yes 78
Precomfort cooling setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Precomfort heating setpoint 0 1 1 1 0 9.001 DPT_Value_Temp No 70
Presence detector input 0 1 1 0 0 1.018 DPT_Occupancy No 38
Room dewpoint alarm input 0 1 1 1 1 1.005 DPT_Alarm Yes
Room temperature input 0 1 1 1 1 9.001 DPT_Value_Temp Yes 77
Setpoint ... (6 indiv. values) 0 1 1 0 0 9.001 DPT_Value_Temp No 70
Setpoint offset 0 1 1 0 0 9.002 DPT_Value_Tempd No 72
Setpoints cooling 0 1 1 0 0 222.100 DPT_TempRoomSetpSetF16[3] No 70
Setpoints heating 0 1 1 0 0 222.100 DPT_TempRoomSetpSetF16[3] No 70
Setpoint shift cooling 0 1 1 0 0 222.101 DPT_TempRoomSetpSetShiftF16[3] Yes 72
Setpoint shift heating 0 1 1 0 0 222.101 DPT_TempRoomSetpSetShiftF16[3] Yes 72
Status request 0 1 1 0 0 C.S.
1)
1 Byte No 117
Temporary Comfort mode 0 1 1 0 0 1.017 DPT_Trigger No 40
Triac Y1 0 1 1 0 0 1.001 DPT_Switch No 112
Triac Y2 0 1 1 0 0 1.001 DPT_Switch No 112
Triac Y3 0 1 1 0 0 1.001 DPT_Switch No 112
Triac Y4 0 1 1 0 0 1.001 DPT_Switch No 112
Schedule occupancy 0 1 1 0 0 20.003 DPT_OccMode Yes 37
Schedule room operating
mode
0 1 1 0 0 20.102 DPT_HVACMode Yes 47
Schedule usage 0 1 1 0 0 20.002 DPT_BuildingMode Yes 36
Window switch input 0 1 1 0 0 1.019 DPT_Window_Door No 34