Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
115/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies Room unit 21 Sep 2010
The measured value of the integrated temperature sensor can be corrected to
compensate e.g. wall installation issues.
Parameter Basic setting Range Resolution HandyTool
Measured value correction 0 K – 3 ... 3 K 0,1 K *101
This correction is also valid for a sensor that is connected to the analog input B1 (but
not for a bus sensor).
The maximum setpoint shift range is as follows (see also page 72).
Parameter Basic setting Range Resolution HandyTool
Setpoint offset range ± 3 K ± 0 ... 10 K 1 K *103
A central station together with communication object
Enable comfort (see page 57)
can prevent the room operating mode from being more than
Economy (to save energy).
Enable Comfort, however, can be ignored in the room controller via the following
parameter:
Parameter Description HandyTool
Local Comfort mode
Change from Economy to Precomfort or Comfort mode.
*105
Enabled (basic setting)
Precomfort or Comfort can be disabled via the Enable
Comfort
input.
1
Disabled (ignore Enable Comfort input). Precomfort or
Comfort CANNOT be disabled via the Enable Comfort
input.
0
You can choose whether or not the room unit has an LCD display. If yes, the following
parameters can also be set.
Beim HandyTool ist fix "Mit LCD" eingestellt.
Parameter Description Basic setting
Room unit Without LCD / with LCD Without LCD
The display of the heating and cooling symbols can be enabled or disabled. Note that
this applies only to room units with an LCD display.
Symbols:
Cooling sequence active
Heating sequence active
Parameter Description Basic setting
Show heating/cooling symbols Displays heating and cooling symbols. Enabled
The room temperature can be displayed either in Celsius (°C) or Fahrenheit (°F). Note
that this applies only to room units with an LCD display.
Parameter Value HandyTool
Temperature unit (Only room units with LCD). *108
Celsius (°C) (basic setting). 1
Fahrenheit (°F) 0
Sensor correction
Note
Setpoint shift range
Local Comfort mode
(LTE mode only)
Room unit
Display heating and
cooling symbols
(ETS only)
Select temperature unit