Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- CLC and RAD description of functions for CC-02
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communications mode
- 4 Applications / Parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode with DESIGO (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode via room operating mode schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 DESIGO examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via window contact input
- 5.4.2 Central control of room operating mode with an input from the room operating mode schedule
- 5.4.3 Central control of the room operating mode via the schedules Use and Occupancy
- 5.4.4 Central and local control of room operating mode based on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via window contact input
- 5.5.2 Central room operating mode control via Enable Comfort
- 5.5.3 Central control of room operating mode via room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE mode examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Master/slave
- 10 General / central functions
- 10.1 Send heartbeat and Receive timeout
- 10.2 Digital inputs
- 10.3 Temporary Comfort mode
- 10.4 Presence detector switch-on and switch-off delay
- 10.5 Heating and cooling demand
- 10.6 Heating/cooling signal output
- 10.7 Special functions
- 10.8 Morning boost (Morning Warmup, 2)
- 10.9 Precooling (Precool, 5)
- 10.10 Test mode (Test, 7)
- 10.11 Emergency heat (8)
- 10.12 Free cooling (Freecool, 10)
- 10.13 Alarm
- 10.14 Reset setpoint shift
- 10.15 Free inputs/outputs
- 10.16 Software version
- 10.17 Device state
- 11 Room unit
- 12 KNX information
- 12.1 Reset and startup response
- 12.2 LED flashing pattern
- 12.3 Startup delay
- 12.4 Bus load
- 12.5 S-mode communication objects for RAD/CLC
- 12.6 LTE-mode communication objects
- 12.7 HandyTool parameters by number
- 12.8 HandyTool parameters, alphabetical
- 12.9 HandyTool enumerations
- 12.10 Data point type description
- 13 FAQ
- 14 Integration of RXB in DESIGO/Synco
- 14.1 Case 1: Integration in Synco
- 14.2 Case 2: Integration in DESIGO
- 14.3 Case 3: Display in DESIGO, with shared Synco schedule
- 14.4 Case 4: Display in DESIGO/Synco, with shared Synco schedule
- 14.5 Case 5: Display in DESIGO, separate schedules
- 14.6 Case 6: Separate display, separate schedules
- 14.7 Case 7: Separate display, shared Synco schedule
- 15 Working with different tools
110/140
Siemens RXB (KNX) Applications library CLC and RAD description of functions for CC-02 CM110384en_04
Building Technologies General / central functions 21 Sep 2010
10.13.2 LTE mode
Enable alarm info can also be operated in LTE mode. Here, two types of information
are provided:
AlarmInfo_CS and AlarmText_CS.
With Synco, the user does not need to deal with this, as connection is opened
automatically.
The device in this case is active on the bus and sends its alarm as soon as it receives
highest alarm priority. This ensures that the control station does not miss alarms.
AlarmInfo_CS (Output)
Possible partner function blocks
Known partner devices
AlarmInfo_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
AlarmText_CS (Output)
Possible partner function blocks
Known partner devices
AlarmText_CS
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Enable alarm info (input)
Possible partner function blocks
Known partner devices
EnableAlarmInfo
Broadcast
Siemens
Synco RMU710 / 20 / 30,
RMH760, RMB795, RMS705
Error code English
4910
RXB room temp. sensor error
4930 RXB room air condensation
4960 RXB general fault
4970
RXB PPS fault
For more information on the alarm concept, refer to "Communication via bus, Synco700
& RXB", CE1P3127.
10.14 Reset setpoint shift
When the system changes from Comfort or Precomfort to Economy or Protection, the
setpoint shift can be reset (see page 72). This function can be enabled and disabled via
Central functions.
The setpoint shift can only be reset with the QAX34.1 and QAX84.1 room units, which
have an LCD display. Enabling this function in room units with a mechanical setpoint
shift (potentiometer) causes data transmission errors.
HandyTool
Parameter Short name Range Basic setting
*137 Reset setpoint shift 0 = Disabled
1 = Enabled
Disabled
KNX
R
CO
Display on Synco
device:
STOP
Important!