Operating Instructions

12/16
Siemens RXB application library (KNX) CM110671en_02
Building Technologies CLC & RAD – chilled ceiling and radiator applications from CC-02 14.03.2008
CLC02 – Chilled ceiling and radiator
Application CLC02 includes the following functions
(refer to the description of functions CM110384 for detailed information):
Function
Brief description
Continuous heating and
cooling sequence.
– PI control.
Two proportional control sequences, heating and cooling.
Control of thermal / electromechanic / motorized valve actuators (AC 24 V, PDM /
AC 24 V, 2-position / AC 24 V, 3-position).
Control of motoric KNX bus valve actuators
– Downdraft compensation
Valve exercising feature.
Dewpoint sensor. Dewpoint sensor to prevent condensation.
Temperature measurement. Via room unit or passive temperature sensor.
Outside temperature (for
downdraft compensation).
Via KNX bus.
Room operating modes. Comfort, Precomfort, Economy and Protection mode.
Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift. Locally via room unit or centrally.
General functions. Presence detector.
– Window contact.
– Master/slave operation.
Boost heating, night cooling etc.
– Free inputs/outputs.
Room units.
Versions available with temperature sensor, setpoint shift,
/Auto switch and LCD display.
Compatible controllers. CLC02 runs on RXB24.1/CC-02
Functions