Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 1BFNC02 Two-pipe fan coil with changeover 2013-06-07
Menu
Parameters.
Values/Range
Basic setting
Fan control All
Minimum on time
1...10 min
6 min
Temperature sensor B1
Room
Return air
Measured value only
No sensor
No sensor
Periodic fan kick Comfort
FC-13: also Precomfort
0...90 min (90min = Off) 90 min (Off)
Periodic fan kick Economy
0...360 min (360min = Off)
360 min (Off)
Room unit Measured value correction 3...3 K 0 K
Setpoint offset range
± 0...10 K
± 3 K
Local Comfort mode
Enabled / Disabled
Enabled
Room unit
Without LCD / with LCD
Without LCD
With LCD
Display heating/cooling symbols
Enabled / Disabled
Enabled
Temperature unit °C or °F °C
Standard display No display / Room temperature
/ Setpoint
Additional for RXB39.1:
Setpoint + scale setpoint shift /
Room temperature + scale
setpoint shift
Room temperature.
Setpoint display
Absolute / Relative
Relative
DC 0...10 V
Fan function standby
0 / 1
Disabled (0)
Fan speed user defined
0 / 1
Disabled (0)
User fan speed 3 0...100% (of Smin-Smax) 100 %
User fan speed 2
0…100% (of Smin-Smax)
50 %
User fan speed 1
0…100% (of Smin-Smax)
0 %
General functions
Digital input 1...4
Free (bus = 1) = Contact open/closed
Free (bus = 1)
Occupancy: Occupied = Contact open/closed
= Contact closed.
Window: Window open = Contact open/closed
FC-13 only
Air flow No air flow = Contact open/closed
Temporary Comfort mode
0...360 min
60 min
On-delay occupancy detector
0...90 min
5 min
Off-delay presence detector
0...90 min
5 min
Central functions
Heating demand signal
Enabled / Disabled
Enabled
Cooling demand signal
Enabled / Disabled
Enabled
Boost heating
Enabled / Disabled
Enabled
Precooling, free cooling
Enabled / Disabled
Enabled
Reset setpoint offset Enabled / Disabled Disabled
Master/slave
Master/slave
Master or slave
Master
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, RXB device name, type code and application
group.
15 Room controllers RXB21.1 with application group FC-10 RXB21.1/FC-10
The controllers are delivered with the basic settings shown above.
Ordering
Example
Note