Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 9BFNC20 Four-pipe fan coil, controlled by one damper 2013-06-07
Four-pipe fan coil, controlled by one damper
FNC20
Heating with LTHW and cooling with CHW.
3-position damper actuator.
Automatic or manual fan control.
Plant diagram
N1 Room controller.
R1 Room unit with temp.
sensor.
B1 Return air sensor.
D1 Window switch.
D2 Presence detector.
Q1 Fan (1… 3-speed).
YM 3-position damper actuator.
10385S22
T
B1
Q1
N1
R1
D1 D2
T
YM
KNX
R
Operating diagrams
Y Output signal.
TR Room temperature.
SpH Effective heating setpoint.
SpC Effective cooling setpoint.
H Heating sequence.
C Cooling sequence.
YM Damper actuator.
Q14 Fan speed 1.
Q24 Fan speed 2.
Q34 Fan speed 3.
10385D52
100
TR [°C]
Y [%]
SpH SpC
YM
H C
0
N
TR [°C]
Y
H
C
Q14
Q24
Q34
SpH SpC
10385D53