Siemens RXB application library (KNX) RXB – Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 9BFNC20 – Four-pipe fan coil, controlled by one damper 2013-06-07
Four-pipe fan coil, controlled by one damper
FNC20
• Heating with LTHW and cooling with CHW.
• 3-position damper actuator.
• Automatic or manual fan control.
Plant diagram
N1 Room controller.
R1 Room unit with temp.
sensor.
B1 Return air sensor.
D1 Window switch.
D2 Presence detector.
Q1 Fan (1… 3-speed).
YM 3-position damper actuator.
10385S22
T
B1
Q1
N1
R1
D1 D2
T
YM
KNX
R
Operating diagrams
Y Output signal.
TR Room temperature.
SpH Effective heating setpoint.
SpC Effective cooling setpoint.
H Heating sequence.
C Cooling sequence.
YM Damper actuator.
Q14 Fan speed 1.
Q24 Fan speed 2.
Q34 Fan speed 3.
10385D52
100
TR [°C]
Y [%]
SpH SpC
YM
H C
0
N
TR [°C]
Y
H
C
Q14
Q24
Q34
SpH SpC
10385D53