Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 7BFNC12 Four-pipe fan coil with outside air damper 2013-06-07
Application FNC12 includes the following functions
(refer to the description of functions CM110385 for detailed information):
Function Brief description)
Four-pipe fan coil.
PI control.
Two proportional control sequences, heating and cooling.
Control of thermal valve actuators (AC 24 V, PDM).
Control of motorized KNX bus actuator valves.
Outside air damper.
Valve exercising feature.
Fan control.
1...3-speed automatic.
Manual with room unit.
Temperature measurement. Room temperature sensor or
Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift. Locally via room unit or centrally.
General functions. Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling.
Free inputs / outputs
Room units. Available with temperature sensor, setpoint adjuster,
button for /Auto and fan speed control, and LCD display.
Compatible controllers.
FNC12 is supplied with RXB21.1/FC-11.