Operating Instructions
Table Of Contents
- RXB applications library (KNX)
- RXB – Fan coil applications from FC10, FC11, FC12, FC-13
- FNC02 - Two-pipe fan coil with changeover
- FNC03 - Two-pipe fan coil with changeover and electric reheater
- FNC04 - Four-pipe fan coil
- FNC05 - Four-pipe fan coil with electric reheater
- FNC08 - Four-pipe fan coil with room supply air cascade
- FNC10 - Two-pipe fan coil with changeover and outside air damper
- FNC12 - Four-pipe fan coil with outside air damper
- FNC18 - Two-pipe fan coil (changeover) and radiator
- FNC20 - Four-pipe fan coil, controlled by one damper
37/54
Siemens RXB application library (KNX) RXB – Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies – Two-pipe fan coil with changeover and outside air damper 2013-06-07
Menu
Parameters.
Values/Range
Basic setting
Central functions
Heating demand signal
Enabled / Disabled
Enabled
Cooling demand signal
Enabled / Disabled
Enabled
Boost heating
Enabled / Disabled
Enabled
Precooling, free cooling Enabled / Disabled Enabled
Rapid ventilation
Enabled / Disabled
Enabled
Night purge
Enabled / Disabled
Enabled
Reset setpoint offset
Enabled / Disabled
Disabled
Master/slave
Master/slave
Master or slave
Master
The room controllers can be ordered preloaded with the application described here.
When ordering, specify the quantity, RXB device name, type code and application
group.
15 Room controllers RXB21.1 with application group FC-11 RXB21.1/FC-11
The controllers are delivered with the basic settings shown above.
Ordering
Example
Note