Operating Instructions

34/54
Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies Two-pipe fan coil with changeover and outside air damper 2013-06-07
Application FNC10 includes the following functions
(refer to the description of functions CM110385 for detailed information):
Function Brief description)
Two-pipe fan coil..
PI control.
Proportional control sequence, selectable:
Only heating sequence, only cooling sequence or changeover.
Control of thermal or motorized valve actuators
(AC 24 V, PDM / AC 24 V, 2-position / AC 24 V, 3-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
Fan control.
1...3-speed, automatic, or
Manual with room unit.
Temperature measurement. Room temperature sensor or
Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift.
Locally via room unit or centrally.
General functions. Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling.
Free inputs / outputs.
Room units. Available with temperature sensor, setpoint adjuster,
button for /Auto and fan speed control, and LCD display.
Compatible controllers.
FNC10 is supplied with RXB21.1/FC-11.
Functions