Operating Instructions

23/54
Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 4BFNC05 Four-pipe fan coil with electric reheater 2013-06-07
Application FNC05 includes the following functions
(refer to the description of functions CM110385 for detailed information):
Function Brief description)
Four-pipe fan coil.
PI control.
Two proportional control sequences, heating and cooling.
Control of thermal / electromechanic valve actuators
(AC 24 V, PDM or AC 24 V, 2-position).
Control of motorized KNX bus actuator valves.
Valve exercising feature.
Electric air heater.
2-position or proportional control.
Control: AC 24 V, 2-position or proportional.
Fan control. 1...3-speed
Automatic, or
Manual with room unit.
Temperature measurement. Room temperature sensor or
Return air sensor.
Room operating modes. Comfort, Precomfort, Economy and Protection mode..
Change of operating mode via
/Auto switch on room unit, presence detector,
window contact or central command.
Setpoint shift.
Locally via room unit or centrally.
General functions. Presence detector.
Window switch.
Master/slave operation.
Boost heating, night cooling etc.
Free inputs/outputs.
Room units. Available with temperature sensor, setpoint adjuster,
button for /Auto and fan speed control, and LCD display.
Compatible controllers.
FNC05 is supplied with RXB22.1/FC-12.
Functions