Operating Instructions

15/54
Siemens RXB application library (KNX) RXB Fan coil applications from FC-10, FC-11, FC-12, FC-13 CM110672en_05
Building Technologies 3BFNC04 Four-pipe fan coil 2013-06-07
Four-pipe fan coil
FNC04
Heating with LTHW and cooling with CHW.
Modulating control of heating and cooling valve.
Automatic or manual fan control.
Plant diagram
N1 Room controller.
R1 Room unit with temp.
sensor.
B1 Return air sensor.
D1 Window switch.
D2 Presence detector.
Q1 Fan (1… 3-speed).
YH Heating valve.
YC Cooling valve.
10385S12
T
B1
YC
YH
Q1
N1
R1
D1 D2
T
KNX
R
Operating diagrams
Valves
100
0
TR [°C]
Y [%]
SpH SpC
YC
YH
H
C
10385D35
1-2-3 speed fan
Y Output signal.
TR Room temperature.
SpH Effective heating setpoint.
SpC Effective cooling setpoint.
H Heating sequence.
C Cooling sequence.
YH Heating valve.
YC Cooling valve.
Q14 Fan speed 1.
Q24 Fan speed 2.
Q34 Fan speed 3.
TR [°C]
Y
H
C
Q14
Q24
Q34
SpH SpC
10385D36