Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
8.3.1 4-pipe fan-coils with electric reheater
The controller operates with a PI algorithm optimized for 2-position / modulating
reheaters (RXB2...) or proportional DC 0...10 V reheaters (RXB39.1).
For simplicity, the diagrams below only show the P-control action.
T
T
B1
YC
YH
Q1
Y Output signal
TR Room temperature
SpC Effective cooling setpoint
SpH Effective heating setpoint
H Heating sequence
C Cooling sequence
YH Heating valve
YC Cooling valve
YR Electric reheater
D3 Safety thermostat
B1 Return air sensor
Q1 Fan
1-step
Modulating
OFF
YR
ON
0%
Y
100%
YC
YH
TR [°C]
YR
H
1 K
SpH SpC
10385D54
YC
YH
0%
TR [°C]
YR, Y
100%
H
SpH
SpC
YR
10385D55
8.3.2 2-pipe fan-coils with electric reheater
The controller operates with a PI algorithm optimized for 2-position / modulating
reheaters (RXB2...) or proportional DC 0...10 V reheaters (RXB39.1).
For simplicity, the diagrams below only show the P-control action.
T
B1
YHC
Q1
T
YHC Heating valve
YR Electric reheater
D3 Safety thermostat
B1 Return air sensor
Q1 Fan