Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
The two fields at the bottom of the dialog box only appear if "LTE and S-mode" was
selected under Communication.
Select Sequences.
HandyTool See parameters in the last column of the table below
Short name
Range
Basic setting
HandyTool
Heating outp bus valve
Heating coil outp bus valve
0 = Disabled / Off
1 = Enabled / On
Disabled (0) *085
Cooling outp bus valve
Cooling coil outp bus valve
0 = Disabled / Off
1 = Enabled / On
Disabled (0) *087
8.1.6 Valve exercising feature
To prevent valves from seizing after long periods of inactivity (e.g. cooling valves in
winter) the valves are operated from time to time. The valve actuators are operated in
such a way as to waste as little heating or cooling energy as possible.
The valve exercise function is triggered if the valve has been closed for ca. 91 hours
without interruption.
Note
ACS