Operating Instructions

Table Of Contents
90/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
Select Sequences; Running time …. and Sequences; Positioning signal …. :
HandyTool See Parameter number in the last column of the table below
3
rd
party actuators.
Parameters 4-pipe
Basic setting
Range
Resolution
HandyTool
Running time heating valve
120 s
0...360 s
1 s
*061
Running time cooling valve
120 s
0...360 s
1 s
*062
Positioning signal max value
10 V
0...10 V
0.1 V
*068
Positioning signal min value
0 V
0...10 V
0.1 V
*069
You can select different running times for the heating and cooling actuators, but only
common values for min. and max. positioning signal.
Parameters 2-pipe
Basic setting
Range
Resolution
HandyTool
Running time heating / cooling valve
120 s
0...360 s
1 s
*061
1)
Positioning signal max value
10 V
0...10 V
0.1 V
*068
Positioning signal min value
0 V
0...10 V
0.1 V
*069
1) In the case of 2-pipe applications (changeover), parameter *062 (Running time
cooling valve) is visible in the HandyTool, but has no effect.
ACS
Note