Operating Instructions

Table Of Contents
84/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Control sequences 2013-06-17
The changeover information must be transmitted to the bus and is integrated via the
following communication object:
H/C changeover input (Input communication object)
Flags
Type Receive timeout
Value
R
W
C
T
U
0 1 1 0 0 1.100
DPT_Heat/Cool
yes
0 = Cooling
1 = Heating
The following communication object is used in LTE-mode:
H/C changeover (Input)
Possible partner function blocks
Known partner devices
ChangeOverStatusWater
342 WCOS
Water Changeover Status Sensor
Siemens:
Synco RMU710 / 20 / 30
RMB795 / RMS705
Distribution zone, heating
Distribution zone, cooling
8.1.3 Heating/cooling output
The controller makes its status (heating or cooling) available via the following
communication object:
Heating/cooling output (Output communication object)
Flags
Type Send heartbeat
Value
R
W
C
T
U
1 0 1 1 0 1.100
DPT_Heat/Cool
yes
0 = Cooling
1 = Heating
The value of the Output as a function of the room temperature is shown in the following
diagram:
0 = Cool
TR
10385D201
SpH SpC
1 = Heat
Value
8.1.4 Actuator type selection
All actuators have threads suitable for fitting to both normally-closed (push to open) and
normally-open (pull-to-open) valves. However, the RX applications do not support
inverse control, which means that only actuators with a pulling action can be used with
"pull-to-open" valves and only actuators with a pushing action can be used with "push-
to-open" valves. This is why, in RX applications, valves with mounted actuators are
always closed when de-energized.
CO
STOP
Note!