Operating Instructions

Table Of Contents
78/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Temperature measurement 2013-06-17
Room temperature output (Output communication object)
Effective room temperature (Output communication object)
Return air temperature output (Output communication object)
Flags
Type Send heartbeat Value
R
W
C
T
U
1 0 1 1 0 9.001
DPT_Value_Temp
yes Floating point (°C)
Invalid temperatures are mapped to the bus as 0 °C.
In LTE mode, the room/return air temperature from directly connected sensors is
mapped as follows:
Room temperature output (Output)
Possible partner function
blocks
Known partner devices
TempRoom
390 UHD
UserHVACDisplay
Siemens:
Synco RMH760 / RMB795
RMU710 / 20 / 30
Geographical zone
Return air temperature output (Output)
Possible partner function
blocks
Known partner devices
TempReturnAir
--- ---
Geographical zone
7.1.6 Temperature sensor input from Konnex bus
The signal from the sensor connected to the bus takes priority. The signal is not
averaged and no sensor correction (page 157) is done.
Since KNX temperature sensors are available from a variety of manufacturers, the
name of the S-mode output communication object varies accordingly.
RaumTemperatur
EffektiveRaumTemperatur
10385Z16en
Room temperaure Input Effective Room temperature
Effective Room Temperature
... or ...
Return air temperature Input
KNX temperatur sensor RXB... room controller
If the room temperature/return temperature is available as information on the bus, it can
be read with one of the following S-mode communication objects:
Room temperature input (Input communication object)
Return air temperature input (Input communication object)
Flags
Type Receive timeout Value
R
W
C
T
U
0 1 1 1 1 9.001
DPT_Value_Temp
yes Floating point (°C)
Note
CO