Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
73/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Setpoint calculation 2013-06-17
In a building automation and control system, the central setpoint shift can be influenced
via the following S-mode communication objects (triplets):
Setpoint shift for heating (Input communication object)
Setpoint shift for cooling (Input communication object)
Flags
Type Receive timeout States
R
W
C
T
U
0 1 1 0 0 222.101
DPT_TempRoomSetp
SetShiftF16[3]
yes
3 floating point values
– Comfort (K)
– Precomfort (K)
– Economy (K)
In LTE-mode, the central setpoint shift is transmitted via the following communication
objects (triplets):
Setpoint shift for heating (Input)
Setpoint shift for cooling (Input)
Possible partner
function blocks
Known partner devices
TempRoomSetpSetHeatShift
TempRoomSetpSetCoolShift
115 HVACOPT
HVAC Optimizer
Siemens:
Synco RMB795
Geographical zone
6.5 Local setpoint shift
If setpoints are shifted locally and corrected by the controller, local shift is applied.
Two methods are available for local setpoint shift:
– Using a series QAX... room unit (local PPS bus) providing a rotary button or rocker
switch to adjust the room temperature setpoint
– or via KNX bus.
If multiple sources command local setpoint shift, "last one wins" applies.
The S-mode communication object is used for setpoint shift via the EIB/KNX bus:
Setpoint offset (input communication object)
Flags
Type Receive timeout Value
R
W
C
T
U
0 1 1 0 0 9.002
DPT_Value_Tempd
No Floating point (K)
The following communication object is used in LTE-mode:
Setpoint offset (input)
Possible partner
function blocks)
Known partner devices
TempRoomSetpUserOffset
384 UHRS
User HVAC
Room settings
Siemens:
Synco QAW740
Geographical zone
CO
CO