Operating Instructions

Table Of Contents
72/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Setpoint calculation 2013-06-17
In LTE-mode, the central setpoint setting is transmitted via the following communication
objects (triplets).
Setpoints heating (Input)
Setpoints cooling (Input)
Possible partner
function blocks
Known partner devices
TempRoomSetpSetHeat
TempRoomSetpSetCool
Siemens SBT proprietary
Siemens:
Synco RMB795
Geographical zone
Setpoints that have been changed by a tool (e.g. HandyTool) are overwritten by
PX-KNX during start-up of the room controller!
6.4 Central setpoint shift
The Comfort, Economy and Precomfort setpoints can be adjusted centrally for
heating and cooling via the building automation and control system.
Central setpoint shifts are used particularly e.g. for summer/winter compensation.
Summer/winter compensation causes a gradual increase in room temperature as a
function of the outside temperature. This prevents too great a difference between the
indoor and outdoor temperature in summer and increases overall comfort in winter.
Normally, only Comfort and Precomfort values are shifted.
The room controller corrects the setpoints resulting from central shift by applying the
following rules
Comfort setpoints:
The value for the spacing must not be below the original value
A
.
Precomfort setpoints:
The value for the spacing to Comfort setpoints must not be below the original values
B
.
Winter compensation Original Summer compensation
values
Setpoints
Protection cooling
Economy cooling
Precomfort cooling
Comfort cooling
Comfort heating
Precomfort heating
Economy heating
Protection heating
10385D107
Sp [°C]
T
OA
A
B
STOP
Note!
Management station
Summer/winter
compensation
Internal correction by
controller