Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Setpoint calculation 2013-06-17
HandyTool See Parameters in the last column of the table below
Name
Basic setting
Range 1)
Resolution
Parameter
Protection cooling setpoint
40 °C
10...40 °C
0.5 K
*030
Economy cooling setpoint
35 °C
10...40 °C
0.5 K
*031
Precomfort cooling setpoint
28 °C
10...40 °C
0.5 K
*032
Comfort cooling setpoint
24 °C
10...40 °C
0.5 K
*033
Comfort heating setpoint
21 °C
10...40 °C
0.5 K
*034
Precomfort heating setpoint
19 °C
10...40 °C
0.5 K
*035
Economy heating setpoint
15 °C
10...40 °C
0.5 K
*036
Protection heating setpoint
12 °C
10...40 °C
0.5 K
*037
Frost protection limit value *)
5 °C
2...10 °C *)
0.5 K
*040
1) ACS checks the values / ranges for intersection.
There is no check in ETS and HandyTool.
2) The Frost protection limit can only be changed in applications with an outside air
damper. In the other applications it is fixed at 5°C.
HandyTool: If setpoints are irrelevant for the application (e.g. heating setpoints for
chilled ceiling), they are hidden, and they are set equal to the Protection setpoints
internally.
For reasons of symmetry, all communication objects are always available.
6.3 Setpoint adjustment runtime
The setpoints are stored in the EEPROM so that they are retained when the controller
is reset.
Separate heating and cooling setpoints for Comfort, Precomfort and Economy may also
be defined via the bus, either individually or as triplets.
Economy cooling setpoint (Input communication object)
Precomfort cooling setpoint (Input communication object)
Comfort heating setpoint (Input communication object)
Comfort cooling setpoint (Input communication object)
Precomfort heating setpoint (Input communication object)
Economy heating setpoint (Input communication object)
Flags
Type Receive timeout States
R
W
C
T
U
0 1 1 0 0 9.001
DPT_Value_Temp
no
Floating point (°C)
Setpoints heating (Input communication object)
Setpoints cooling (Input communication object)
Flags
Type Receive timeout States
R
W
C
T
U
0 1 1 0 0 222.100
DPT_TempRoomSetp
SetF16[3]
no
3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
Setpoints
Note