Operating Instructions
Table Of Contents
- RXB (KNX) applications library
- RXB Description of functions for FC10, FC11, FC12, FC13
- Table of contents
- 1 Introduction
- 2 Definitions / Tools
- 3 Select communication mode
- 4 Applications, parameters
- 5 Room operating modes
- 5.1 Description
- 5.2 Overview
- 5.3 Determine the room operating mode in Desigo (S-mode)
- 5.3.1 Local control of room operating mode via a window contact
- 5.3.2 Central control of room operating mode via input from the Use time schedule
- 5.3.3 Central and local control of room operating modebased on occupancy
- 5.3.4 Central control of room operating mode viathe Room operating mode time schedule
- 5.3.5 Local control of room operating mode with a room unit
- 5.3.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.3.7 Effective room operating mode
- 5.3.8 Desigo examples
- 5.4 Determine the room operating mode with third-party products (S-mode)
- 5.4.1 Local control of room operating mode via the window contact input
- 5.4.2 Central control of room operating mode via the Room operating mode time schedule
- 5.4.3 Central control of room operating mode via the Use and Occupancy time schedules
- 5.4.4 Central and local control of room operating modebased on occupancy
- 5.4.5 Local control of room operating mode with a room unit
- 5.4.6 Local control of room operating mode via the Temporary Comfort mode input
- 5.4.7 Effective room operating mode
- 5.4.8 Third-party (S-mode) examples
- 5.5 Determine the room operating mode with Synco (LTE mode)
- 5.5.1 Local control of room operating mode via the window contact input
- 5.5.2 Central control of the room operating mode via Enable Comfort
- 5.5.3 Central control of room operating mode via Room operating mode input
- 5.5.4 Local control of room operating mode via presence detector
- 5.5.5 Local control of room operating mode with a room unit
- 5.5.6 LTE-Mode Examples
- 5.6 Determine the room operating mode without a bus (stand-alone)
- 6 Setpoint calculation
- 7 Temperature measurement
- 8 Control sequences
- 9 Fan control
- 10 Master/slave
- 11 General and central functions
- 11.1 Send heartbeat and receive timeouts
- 11.2 Digital inputs
- 11.3 Temporary Comfort mode
- 11.4 Presence detector switch-on and switchoff delay
- 11.5 Heating and cooling demand
- 11.6 Heating/cooling signal output
- 11.7 Special functions
- 11.8 Boost heating (Morning Warmup, 2)
- 11.9 Night purge (Night Purge, 4), (FNC10, FNC12)
- 11.10 Precooling (Precool, 5)
- 11.11 Test mode (Test, 7)
- 11.12 Emergency heating (Emergency Heat, 8)
- 11.13 Rapid ventilation (Fan only, 9)
- 11.14 Free cooling (Freecool, 10)
- 11.15 Alarm
- 11.16 Reset the setpoint shift
- 11.17 Free inputs/outputs
- 11.18 Software version
- 11.19 Device state
- 12 Room unit
- 13 KNX information
- 14 FAQs
- 15 Integrate RXB in Desigo/Synco
- 15.1 Case 1: Integration into Synco
- 15.2 Case 2: Integration into Desigo
- 15.3 Case 3: Display in Desigo, with shared Synco time scheduler
- 15.4 Case 4: Display in Desigo/Synco, with shared Synco time scheduler
- 15.5 Case 5: Display in Desigo, andseparate time schedulers
- 15.6 Case 6: Separate display, andseparate time schedulers
- 15.7 Case 7: Separate display, andshared Synco time scheduler
- 16 Working with different tools
69/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Setpoint calculation 2013-06-17
6.1.1 Bus output for current setpoints
The present setpoints can be integrated in the building automation and control system
via the following S-mode communication objects individually or as triplets:
Present Eco cooling setp (Output communication object)
Present Precomf cooling setp (Output communication object)
Present Comf cooling setp (Output communication object)
Present Comf heating setp (Output communication object)
Present Precomf heat setp (Output communication object)
Present Eco heating setp(Output communication object)
Flags
Type Send
heartbeat
Values
R
W
C
T
U
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Floating point (°C)
Present setpoints heating (Output communication object)
Present setpoints cooling (Output communication object)
Flags
Type Send
heartbeat
Values
R
W
C
T
U
1 0 1 1 0 222.100
DPT_TempRoomSetpSetF16[3]
yes
3 floating point values
- Comfort (°C)
- Precomfort (°C)
- Economy (°C)
6.1.2 Bus output effective setpoints
For integration into a building automation and control system, the controller maps the
effective setpoints associated with the effective room operating mode to the following
communication object:
Effective setpoint (Output communication object)
Effective setpoint heating (Output communication object)
Effective setpoint cooling (Output communication object)
Flags
Type Send heartbeat Value
R
W
C
T
U
1 0 1 1 0 9.001
DPT_Value_Temp
yes
Floating point (°C)
If the room temperature is in the dead band, the Effective setpoint transmitted by the
controller is either the heating or the cooling setpoint, depending on the controller's last
activity.
6.1.3 Bus outputs LTE mode
In LTE-mode, the current and effective setpoints are not transmitted to the building
automation and control system.
CO
Note