Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Setpoint calculation 2013-06-17
6 Setpoint calculation
6.1 Description
Each room controller has 9 different room temperature setpoints:
One heating and cooling setpoint for the room operating modes Comfort, Precomfort,
Economy and Protection as well as a Frost limit value.
The setpoints
are defined in the tool during engineering.
runtime-adjusted by the communication objects (Desigo, Synco)
This does not apply to the Protection setpoints and the frost setpoint (page 32).
The setpoints are shifted
Centrally via KNX bus from the building automation and control system
(only Comfort, Precomfort and Economy).
Locally via PPS2 by a room unit or a setpoint adjustment unit
(only Comfort and Precomfort).
The controller controls the values internally to ensure that sensible periods are
adhered to between the various room operating modes.
The result is 8 present setpoints.
The effective room operating mode selects one setpoint each for heating and
cooling from the 8 setpoints.
These are the effective setpoints to which the controller executes control.
Define
Shift
Tool 6.2
Runtime 6.3
Centrally 6.4
Locally 6.5
10385Z40en
Comfort heating setpoint
Comfort cooling setpoint
Precomfort heating setpoint
Precomfort cooling setpoint
Economy heating setpoint
Economy cooling setpoint
Protection heating setpoint
Protection cooling setpoint
Local setpoint shift
Central setpoint shift heating
8
present
setpoints
Effective
heating setpoint SpH
Effective
cooling setpoint SpC
H C
PPS2 KNX
Effective
room operating mode
Central setpoint shift cooling
Frost setpoint
KNX
KNX
KNX
KNX
PPS2
DI
KNX
KNX
(6.1.1)
(6.1.2)