Operating Instructions

Table Of Contents
61/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
5.5.6 LTE-Mode Examples
The following examples show two typical applications of the time schedule in
conjunction with local control of the room operating mode.
Rooms with neither a room unit nor a presence detector
The room operating mode in Rooms 1...3 of a building is determined by the
Room operating mode time schedule. Window contacts are fitted in all rooms.
The following conditions are specified:
Overall, the building is in use from 06.00 to 20.00.
The rooms are used and controlled by the Room operating mode time schedule as
follows:
Night setback from 17.00 to 08.00,
– Protection from 20.00 to 06.00
Lunch break from 12.00 to 13.00 (Precomfort)
In Room 3 the window is opened briefly, once in the morning and once at night (1).
Time schedule
Room operating
mode
Window contact
Room 3
Effective room
operating mode
Room 3
Comfort
Precomfort
Economy
Protection
Window open
Window closed
Comfort
Precomfort
Economy
Protection
08:00
17:0013:0012:00
10385D04
1)
06:00
20:00
1)
Rooms with a room unit (
/Auto button) or presence detector
The room operating mode in Rooms 1 and 2 of a building is determined centrally by the
Room operating mode time schedule.
Comfort mode is then initiated locally via the room unit (Room 1) or presence detector
(Room 2).
The following conditions are specified:
Overall, the building is in use from 06.00 to 20.00
(Protection mode from 20.00 to 06.00 hours).
Rooms 1 and 2 must be available from 08.00 to 18.00 hours (Precomfort)
Example 1
Example 2