Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
The following LTE-mode communication object is provided for central control:
Enable Comfort (input)
Possible partner-function blocks Known partner devices
EnableComfort
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programme to HVAC-Mode Conversion
Siemens:
Synco RMB795
Timeswitch zone
The states are:
State Description
Enabled Priority 3 influences (RoomOperatingMode, presence
detector, room unit) are enabled
Disabled Priority 3 influences are disabled.
The effective room operating mode is Economy.
Comfort and Precomfort are enabled locally in the controller with the following
parameter in the Room unit menu, page 155:
Parameter: Local comfort mode
Description
HandyTool
Switch from Economy to Precomfort or Comfort mode
*105
Enabled (basic setting)
Means that Precomfort or Comfort can be disabled via the
Enable Comfort input.
1
Disabled (ignore Enable Comfort input) In this case
Precomfort or Comfort CANNOT be disabled via the
Enable Comfort input
0
5.5.3 Central control of room operating mode via
Room operating mode input
PPS2
Central
(Synco controller)
Local
1.
2.
3.
DI
DI
3.
Controller
3.
Prio
1.
Central (ACS)
0.
The following LTE-mode communication object is used
to control the room operating mode from a building
automation and control system:
Room operating mode (input)
Possible partner-function blocks Known partner devices
HVACMode
110 HVACS
HVAC-Mode Scheduler
104 PMC
Programme to HVAC-Mode Conversion
Siemens:
Synco RMU710 / 20 / 30
RMH760 / RMB795
Timeswitch zone
CO
CO