Operating Instructions

Table Of Contents
55/182
Siemens RXB (KNX) application library RXB Description of functions for FC-10, FC-11, FC-12, FC-13 CM110385en_08
Building Technologies Room operating modes 2013-06-17
The occupant(s) of Room 1 are working overtime. At 18.00 hours the room operating
mode changes to Economy, even if the room unit is set to Auto (1).
Comfort mode can now be re-activated with the Auto switch on the room unit (2).
Comfort remains active for the pre-defined Temporary Comfort mode period (see
page 143).
In Protection mode however, the Temporary Comfort period is also overridden and
the room operating mode changes to Protection (3).
In Room 2, in the evening, there are still people in the room beyond the "building-in-
use" period (4). However, at the end of the building-in-use period the room operating
mode still changes to Protection. An alarm can also be tripped, if required.
Time schedule
room op. mode
Comfort
Precomfort
Economy
Protection
mode
Auto
Comfort
Precomfort
Economy
Protection
mode
Occupied
Unoccupied
Comfort
Precomfort
Economy
Protection
08:00
18:00
10385D05
1)
1)
2)
2)
3)
3)
4)
4)
06:00
20:00
Room with room unit
/Auto button
on the room unit
Room 1
Effective
room op. mode
Room 1
Room without room unit
Presence
detector
Room 2
Effective
room op. mode
Room 2